Mains Input |
| Mains input CE: |
World range 94...136VAC/186...264VAC 47-63Hz, IEC 555
power factor 0,99 nominal EN 61 000-3, -2 |
| Inrush current: |
limited by softstart-circuit, max 16A |
| Power factor: |
0.99, nominal EN 61 000-3, -2 |
| Isolation Inp.-outp. CE : |
EN 60950, ISO 380, VDE 0805, UL 1950,
C22.2.950 |
| Regulation static: |
| 6V |
<25mV (+/-100% load, +/-15% mains) |
| 12V,24V (10A): |
<0.1% (+/-100% load, +/-15% mains) |
|
| dynamic : |
| 6V |
<100mV (+/-25% load) |
| 12V,24V (10/A): |
<0.7% (+/-25% load) |
|
| Recovery time : |
| +/-25% load |
within +-1% |
within +-0,1% |
| 6V |
0.2ms |
0.5ms |
| 12V,24V (10A) |
0.0ms |
1.0ms |
|
| Sense compens.range: |
min. 0.5V |
| Noise and ripple: |
< 10mVpp (0-20MHz ) installed in UEC 01 bin,
<3mVrms |
|
|
EMI |
|
| RFI-rejection (emission) CE: |
EN 50081-1, EN 50022 B (VDE 0871B) |
| EMC (immunity) CE: |
EN 50082-1 |
| Operation temperature: |
0....50°C without derating |
| Storage: |
-30°C up to 85°C |
| Temp.-coefficient: |
< 0.2% / 10K |
| Stability (const. conditions): |
10mV or 0.1% within 24 hours |
| |
50mV or 1.0% within 6 month |
| Current limits: |
115% of rated current-values, adjustable to any lower level (via
fan tray switches or netware). |
| Overvoltage crow bar protection: |
trip off adjusted to 125% of nominal
voltage each output |
| DC Off (trip off): |
within 5ms if >2% deviation from
adjusted nominal values, after overload, overheat, overvoltage, undervoltage
(bad status) and fan fail, output capacitors will be discharged by the crow
bars temperature limits 110°C heat sink, 70°C ambient, trip off points
adjustable, processor controlled. |
| Efficiency: |
> 80% |
| Voltage rise characteristics |
monotone and synchronous, complementary
outputs with dual tracking |